  • Metallic cables
  • Installation

J-Y(ST)Y

...x2x0.6 (0.8) LG

1
2
3
4
5
1

Copper wire

2

Core insulation – PVC

3

Plastic tape

4

Alu/PET tape

5

PVC outer jacket, grey

Transmission element – each 2 wires twisted to a pair. Cable core is transmission elements stranded in layers.

Specification

DIN VDE 0815

Application

» telephone, signaling and data transmission
» permanent installation on and under plaster in dry or damp rooms, permanent installation on external walls

Environmental conditions

Temperature ranges for laying and assembly –5 °C  to +50 °C
Operation and store temperatures – 40 °C to +70 °C
Permitted minimum bending radius min. 10D
Cable lifetime min. 30 years

D – outside cable diameter

Electrical parameters (20 °C)

Conductor diametermm0.6 0.8
Max. loop resistanceΩ/km 130.073.2
Insulation resistance min.GΩ.km100100
Mutual capacitancenF/km1001)1001)
Capacity unbalance k1 at 800 HzpF/100m3002)3002)
Effective test voltage wire/wire at 50 Hz
V800800
Effective test voltage wire/shield at 50 HzV800800
Operating voltage Vss300300

1) in cables up to 4 pairs: 120 nF/km
2) in cables up to 4 pairs only one value can reach max. 500 pF/100 m
2) in cables with more than 4 pairs only 20 % values can reach max. 500 pF/100 m

Wire/core diameter 0.6/0.93 mm Wire/core diameter 0.8/1.43 mm
Number of units External diameter [mm] Net weight [kg/km] Standard production length [m] External diameter [mm] Net weight [kg/km] Standard production length [m]
Stranded in layers
1 4.3 30 100, 250, 500, 1,000 5.4 40 100, 250, 500, 1,000
2 4.5 35 100, 250, 500, 1,000 6.1 55 100, 250, 500, 1,000
3 5.4 45 100, 250, 500, 1,000 7.6 75 100, 250, 500, 1,000
4 5.9 50 100, 250, 500, 1,000 8.4 95 100, 250, 500, 1,000
5 6.4 60 100, 250, 500, 1,000 9.3 115 100, 250, 500, 1,000
6 6.8 75 100, 250, 500, 1,000 9.8 130 100, 250, 500, 1,000
Wire/core diameter 0.6/1.20 mm Wire/core diameter 0.8/1.60 mm
Number of units External diameter [mm] Net weight [kg/km] Standard production length [m] External diameter [mm] Net weight [kg/km] Standard production length [m]
Unit stranding
10 9.0 110 2,000 14.0 200 2,000
20 12.0 195 2,000 19.0 400 2,000
30 15.0 275 2,000 22.0 540 2,000
40 16.5 380 2,000 26.0 780 2,000
50 18.0 430 2,000 28.0 870 1,000
70 21.5 430 2,000 35.0 1,000 1,000
100 24.0 815 1,000 38.0 1,675 1,000
200 40.0 1,500 1,000 51.5 3,100 1,000